Key Points
- Match the sensor's Ex marking to your area classification before comparing features.
- Zone, equipment protection level, gas group and temperature class decide where a sensor can legally go.
- Battery replacement, radio and gateway placement drive the long-term cost of a hazardous-area program.
A wireless condition monitoring sensor belongs on a pump or compressor in a classified area when its certificate covers that area's zone or division, gas group and temperature class. That single check removes more vendors from a shortlist than any feature comparison.
This guide compares four wireless sensors on the hazardous-area ratings their makers publish: Tractian Smart Trac Ultra, Emerson AMS Wireless Vibration Monitor, SKF Enlight Collect IMx-1 and Waites SM7. For a broader view of general-purpose systems, compare the top wireless condition monitoring sensors.
What makes a wireless sensor safe for a hazardous location?
A wireless sensor is safe for a hazardous location when an accredited body has certified it for that area's classification, and the marking on the device matches the zone or division, the gas group and the temperature class of the gas present. Battery-powered sensors usually get there through intrinsic safety: the circuit is designed so it cannot release enough energy to ignite the surrounding atmosphere, even with a fault.
Zones, divisions and what the Ex marking tells you
North American sites mostly classify areas by Class and Division under NEC Article 500. Sites under ATEX (Europe) or IECEx (international) use Zones, and NEC Article 505 brings the Zone system to US plants as well. A marking such as Ex ia IIC T4 Ga reads left to right:
- Ex ia, ib or ic: the intrinsic safety level. "ia" holds up with two faults, "ib" with one, "ic" in normal operation.
- IIC, IIB or IIA: the gas group. IIC covers hydrogen and acetylene and also qualifies for IIB and IIA. A IIB sensor cannot go in a hydrogen area.
- T4: the maximum surface temperature class (135°C for T4). It has to sit below the autoignition temperature of the gas on site.
- Ga, Gb or Gc: the equipment protection level, which maps to Zone 0, Zone 1 and Zone 2.
Decision table: area classification vs minimum rating
Use this table to turn your area classification drawing into a minimum rating before you request quotes.
| Area classification | What it means | Minimum sensor rating | Markings that qualify |
|---|---|---|---|
| Zone 0 | Explosive gas atmosphere present continuously or for long periods | Equipment protection level Ga | Ex ia ... Ga |
| Zone 1 | Explosive atmosphere likely during normal operation | Ga or Gb | Ex ia ... Ga, Ex ib ... Gb |
| Zone 2 | Explosive atmosphere not likely, and brief if it occurs | Ga, Gb or Gc | Ex ia, Ex ib, Ex ic ... Gc, Ex ec ... Gc |
| Class I, Division 1 | Ignitable gas or vapor can exist under normal operating conditions | Listed for Class I, Division 1 in the right group (A to D) | Intrinsically safe for Class I, Div 1 |
| Class I, Division 2 | Ignitable gas or vapor present under abnormal conditions | Listed for Division 1 or Division 2 | Intrinsically safe or nonincendive for Class I, Div 2 |
The rule of thumb runs one way: a sensor rated for a stricter area can go in a less strict one, never the reverse. A Zone 1 sensor works in Zone 2. A Division 2 sensor does not belong in Division 1.
Hazardous location certifications compared
Certificates get renewed and reissued, so ask each vendor for the current certificate for the exact part number you order.
| Rating | Tractian | Emerson | SKF | Waites |
|---|---|---|---|---|
| Sensor | Smart Trac Ultra | AMS Wireless Vibration Monitor | Enlight Collect IMx-1 (CMWA 6100-EX) | SM7 |
| North American hazardous rating | Class I Div 1 certified; NFPA 70 Classes 1 to 3, Division I compliant | Contact vendor for current details | Contact vendor for current details | Contact vendor for current details |
| ATEX | Compliant | Contact vendor for current details | Contact vendor for current details | Contact vendor for current details |
| IECEx | Compliant | Contact vendor for current details | Contact vendor for current details | Contact vendor for current details |
| Highest zone covered | ATEX/IECEx compliant and Class I Div 1 certified | Contact vendor for current details | Contact vendor for current details | Contact vendor for current details |
| Gas group (IEC) | ATEX/IECEx compliant and Class I Div 1 certified | Contact vendor for current details | Contact vendor for current details | Contact vendor for current details |
| Radio and range | 915 MHz ISM, IEEE 802.15.4g to a Tractian receiver; receiver sends over LTE/4G; up to 330 ft indoors, 3,300 ft line of sight | Contact vendor for current details | Contact vendor for current details | Contact vendor for current details |
| Battery | Lithium; up to 5 years on default settings | Contact vendor for current details | Contact vendor for current details | Contact vendor for current details |
| Ingress rating | IP69K | Contact vendor for current details | Contact vendor for current details | Contact vendor for current details |
Tractian Smart Trac Ultra
Best for: Teams that want vibration, ultrasound and temperature from one wireless sensor in classified areas, with automated diagnosis and work orders in the same platform.
Smart Trac Ultra is Tractian's wireless sensor for rotating equipment such as pumps, compressors, fans, agitators and gearboxes. It measures triaxial vibration, ultrasound, temperature and RPM, and it is ATEX/IECEx compliant and Class I Div 1 certified, with NFPA 70 Class 1, 2, and 3 (Division I) compliance.
How it diagnoses
Readings go to the Tractian platform, which compares vibration, ultrasound and temperature on the same asset so a lubrication problem and an early bearing defect show up as different faults. Auto Diagnosis names the likely failure mode, its severity and a recommended action. Tractian reliability engineers add human review when a team wants a second opinion on a finding.
Deployment and hardware
- Fast setup: the sensor mounts with adhesive or drill-and-tap and goes live in minutes, with Tractian specialists supporting the rollout.
- No plant Wi-Fi in the area: sensors talk to a Tractian receiver on 915 MHz, and the receiver sends data over LTE/4G, so no plant network has to run into the classified zone.
- Hazardous and washdown duty: Class I Div 1 rating, IP69K sealing and an operating range of -40°F to 250°F.
- Battery: a lithium cell lasts up to 5 years at the default 10-minute sampling interval.
- Integrations: alerts become work orders inside Tractian and sync to CMMS, ERP and EAM systems such as SAP, Maximo and Oracle NetSuite through Tractian integrations.
Customer results
At ICL, a food-grade phosphate producer, Tractian sensors went on the calciner, drying towers, mills and exhausters. Recurring lubrication alerts on a mill exposed gaps in the maintenance plan, and the plant dropped one of its two annual shutdowns and recovers 400+ tons of output per year.
At Tate & Lyle, the risk sat on fermenter agitators, where a gearbox failure meant 3 to 4 days of downtime and crane work. With 280+ critical assets monitored, the San Diego team avoided 84 hours of downtime, including an unbalance on a dryer bearing. Tractian also supports chemical plants, oil and gas operations and mining sites.
Pricing
Tractian pricing is scoped to your assets. For a hazardous-area rollout, a specialist looks at which pumps, compressors and agitators sit in classified zones, how each one tends to fail, and how many sensors and receivers it takes to cover them, then prices the plan around that risk. Share your asset list and area classification, and Tractian returns a custom quote.
Questions to ask before you buy
- Can one sensor pick up both the vibration of a bearing defect and the ultrasound of a lubrication problem on the same pump?
- Does the platform name the failure mode and recommended action automatically, with human review available?
- Can the sensors run in Class I Div 1 and IP69K washdown areas without plant Wi-Fi?
Emerson AMS Wireless Vibration Monitor
Best for: Sites with an existing WirelessHART network that want triaxial vibration, PeakVue and temperature from a battery-powered sensor.
The AMS Wireless Vibration Monitor measures triaxial vibration, PeakVue, surface temperature and calculated speed, and sends data over WirelessHART (IEC 62591) at 2.4 GHz with 100 m line-of-sight range. The monitor carries Class I Division 1 approval for gas Groups A through D, plus Ex ia IIC T4 Ga under ATEX, IECEx and the US/Canada Zone system.
Notable features
- Data is read in AMS Machine Works and AMS Device Manager software.
- Off-the-shelf battery rated for 3 to 5 years, replaceable in the field in hazardous areas.
- Compatible with existing WirelessHART networks and AMS 9420 Wireless Vibration Transmitters already on site.
Pricing
Emerson does not publish a list price, so ask for a quote that splits the sensor, any WirelessHART gateway the site still needs, and the AMS software license.
Questions to ask before you buy
- Who designs and owns the WirelessHART network if your site has none?
- Where does the gateway sit relative to the classified area?
SKF Enlight Collect IMx-1
Best for: Teams that want a wireless vibration and temperature mesh with SKF software.
The IMx-1 system uses battery-powered sensors that form a Mira mesh network at 2.4 GHz and report to a gateway.
Notable features
- IP69K sensor rated from -40°C to +85°C.
- Bluetooth commissioning from a phone app and over-the-air firmware updates.
- Gateway rated for ATEX and IECEx Zone 2 (Ex ec IIC T4 Gc).
Pricing
No price is published for the IMx-1 EX system. Ask for a quote that covers the EX sensors, the Zone 2 gateway, and the SKF software and services that read the data.
Questions to ask before you buy
- What is the battery life at your temperature and upload rate?
- What does sensor replacement cost at end of life?
- Where does the Zone 2 gateway sit when the sensors are in Zone 1?
- For US Division sites, does a NEC listing exist?
Waites SM7
Best for: Plants that want a wireless triaxial vibration sensor with field-replaceable batteries and analyst support from the vendor.
The SM7 is a high-frequency, triaxial vibration and temperature sensor with wake-on-shake capture for machines that start and stop. It uses IEEE 802.15.4 at 2.4 GHz with 2,100 ft line-of-sight range to Waites gateways. Configurations are available with North American Class I/II Division 1, ATEX and IECEx certifications, plus non-certified versions.
Notable features
- IP69K housing rated from -40°F to 185°F.
- Waites BT7-7000 battery, field replaceable, rated for a 6-year life.
- Human review from Waites analysts on top of machine learning alerts.
Pricing
Waites does not publish SM7 pricing. Request a quote covering certified sensors, nodes, repeaters and the gateway, since the node and repeater carry an IP68 rating and need their own placement plan in classified areas.
Questions to ask before you buy
- What are the exact Ex marking, gas group and certificate number of the SM7 version you order?
- How does the platform flag a repeater that stops relaying or a sensor that comes loose, and who fixes it?
Worked example: which sensors fit a Class I Div 1 pump and a Zone 1 hydrogen compressor
Take two assets and run them through the certification table.
Asset 1: a centrifugal pump moving toluene in a Class I, Division 1, Group D area at a US chemical plant. Toluene falls in Group D, and its autoignition temperature sits well above the 135°C limit of T4. The sensor needs a Class I Division 1 listing.
- Smart Trac Ultra from Tractian, the Emerson monitor (Groups A through D) and the Waites SM7 Division 1 configuration carry a published Class I Div 1 rating.
- The SKF CMWA 6100-EX carries ATEX and IECEx Zone 1 ratings; check with your authority having jurisdiction whether they are accepted for a Division-classified area.
Asset 2: a hydrogen recycle compressor in a Zone 1, IIC area at a European refinery. The sensor needs equipment protection level Ga or Gb and gas group IIC.
- Emerson (Ex ia IIC T4 Ga) and SKF (Ex ib IIC T4 Gb) match on paper. The SKF gateway is rated for Zone 2, so it goes outside the Zone 1 boundary.
- Waites offers SM7 configurations with ATEX and IECEx certifications. Ask Waites for the Ex marking that confirms Zone 1 and IIC for the part you order.
The same steps work for your own plant: pull the area classification drawing, note the zone or division, gas group and temperature class for each asset, and strike any sensor whose marking falls short before you look at software.
Questions to ask any vendor before a hazardous-area rollout
- What is the certificate number, so your EHS team can check the marking against the area drawing?
- Where do the gateway, repeaters or receivers sit, and what rating does that network hardware carry?
- Can batteries be swapped in the classified area, or does the sensor have to come out?
- Does a battery swap need a hot-work permit at your site?
- How does a fault called in an Ex area reach the planner as a work order?
For the trade-offs between cabled and battery systems, compare wireless vs wired condition monitoring. For vendor-by-vendor detail, read SKF alternatives and Tractian vs Waites.
Frequently Asked Questions
What does intrinsically safe mean for a wireless vibration sensor?
An intrinsically safe sensor limits the electrical and thermal energy in its circuit, including the battery, so it cannot ignite the gas or dust around it. The protection level shows in the marking: Ex ia tolerates two faults, Ex ib one, and Ex ic covers normal operation. Check the level against your zone before installing.
Can a Class I Division 2 sensor be used in a Division 1 area?
No. Division 2 equipment is designed for areas where ignitable gas appears under abnormal conditions, not in normal operation. A Division 1 area needs equipment listed for Division 1, such as an intrinsically safe sensor rated for the right gas group. Division 1 equipment can go in Division 2 areas.
Is ATEX certification accepted in the United States?
ATEX is a European Union requirement, and US installations are governed by the NEC and the local authority having jurisdiction. US sites usually require a North American listing (Class and Division, or AEx Zone marking under NEC Article 505). Ask your EHS or electrical engineer which listings your site accepts.
Do wireless gateways need a hazardous-area rating too?
Any device installed inside a classified area needs a rating for it, gateways and repeaters included. Many network devices carry a lower rating than the sensors, for example Zone 2 at most, so they get placed outside the stricter zone. Check the range from that location before you commit to a layout.
How often do batteries need replacing in hazardous-area sensors?
Battery life depends on sampling rate, temperature and radio conditions; Tractian sensors run up to 5 years on default settings. Some designs allow field replacement inside the area, while others need the full sensor swapped. Ask for the battery life at the sampling rate you plan to use.
Start monitoring classified-area assets
Tractian sensors pair a Class I Div 1 rating with vibration, ultrasound and temperature in one housing, report over LTE without plant Wi-Fi, and send diagnosed faults straight into work orders. See how Tractian condition monitoring covers pumps, compressors and agitators in hazardous areas.